Skip to content Skip to footer
GMTCNT

GTC-ETCH

8 Channel EtherCAT Module

  • Digital calibration technology for input measurement.
  • Supports various thermocouples and RTDs.
  • Auto tuning (AT) control.
  • DIN rail mounting.
  • User-friendly operation interface.
  • Can be easily adapted to your panels with a 24 VDC power supply.
  • Enhanced anti-interference capability developed for operation in adverse industrial environments.

Technical Specifications

  • Supply: 24 VDC (-15%, +10% tolerance)
  • Power Consumption: ≤ 5W
  • Supported Sensor Types:
    • Thermocouple: K, S, R, E, J, T, B, N, WRe3-WRe25, WRe5-WRe26
    • RTD: Cu50, Pt100
    • DC Voltage: 0~5V, 1~5V, 0~1V, 0~100mV, 0~20mV, 0~500mV, etc.
    • DC Current: 4~20mA (with 250 Ohm shunt resistor)
  • Reading Range (Temperature):
    • K (-50~1300°C), S and R (-50~1700°C), T (-200~ +350°C), E (0~800°C), J (0~1000°C), B (200~1800°C), N (0~1300°C)
    • Cu50 (-50~ +150°C), Pt100 (-200~ +600°C)
  • Measurement Accuracy: 0.25%FS ± 1 measured unit
  • Control Period (Cycle Time): 0.24~300.0 seconds selectable, and this value must be in integer multiples of 0.5 seconds.
  • Control Mode: On-Off control mode (deadband adjustable). Fuzzy logic PID control, auto-tuning with AI-PID (advanced artificial intelligence algorithm).
  • Output Specifications: SSR Output: 12VDC/30mA (for driving SSR)
  • Sampling Period: Can sample 8 times per second. Response time can be set to 0.5 seconds (by setting the digital filter parameter FILt=0).
  • Function (Alarm): Upper limit, lower limit, deviation upper limit, deviation lower limit.
  • Electromagnetic Compatibility (EMC): ± 4KV/5KHz according to IEC61000-4-4; 4KV according to IEC61000-4-5.
  • Isolation Withstand Voltage: ≥ 600V between terminals.
  • Operating Conditions: Temperature -10~60°C, Humidity ≤ 90%RH
  • Communication: Modbus RTU (RS485) 9600, 8, None, 1