GHPro2-070E2
Developed for use in industrial applications, this HMI operator panel offers stable and reliable performance in most industrial environments within an operating temperature range of 0–50°C. Its front panel complies with NEMA 1 standards and is designed considering industrial usage requirements. When appropriate precautions are taken against electrostatic noise and electromagnetic effects, it ensures long-term and stable use in production areas.
The device operates with DC 10–28V input voltage and offers basic protection against overvoltage situations thanks to its internal fuse. It is designed to be compatible with switching power supplies in the power feed, and system safety can be increased with the use of shielded cables and correct grounding. Separation of DC and AC power lines supports system stability and safe operation. The power connection can be made easily and safely through the terminal located on the rear panel; it provides seamless integration into industrial automation systems thanks to DC24V, GND, and FG terminals.
- Display Type: 7” TFT
- Resolution: 1024 x 600
- Color: 16.77M
- Backlight: LED
- Brightness: 450cd/m²
- Backlight Life: >30,000 hours
- Touch Screen: 4-wire precision resistance circuit
- Processor: ARM Cortex-A7 Dual Core 1GHz
- Memory: 256 MB NAND Flash + 128 MB DDR3 Memory
- RTC: Available
- Expansion Memory: –
- Printer Port: USB Slave (Pictbridge)
- Ethernet: –
- Program Upload: MICRO USB / RS-232
- COM Port:
- COM0: RS-232, RS-485, RS-422
- COM2: RS-232
- Power Consumption: 2.4W
- Operating Voltage: 24VDC
- Input Range: 10VDC – 28VDC
- Momentary Power Interruption: <3ms
- Scale Isolation Resistance: >50MΩ (500VDC)
- Dielectric Strength Test: 500VAC 1 minute
- Case Material: Engineering Plastic
- Dimensions (mm): 132 x 102 x 33
- Panel Cutout Size (mm): 119 x 93
- Weight (kg): 0.21
- Operating Temperature: Between 0 and 50°C
- Operating Humidity: Between 10%rH and 90%rH, non-condensing
- Storage Temperature: Between -20 and 60°C
- Storage Humidity: Between 10%rH and 90%rH, non-condensing
- Impact Resistance Test: Between 10Hz and 25Hz (X, Y, Z direction, 30 minutes)
- Cooling Method: Air cooling
- Protection Class: IP65 (front panel)
- Standards: CE marked, EN61000-6-2:2005/EN61000-6-4:2007+A1:2011