GXM-40UA
Domestically Produced Temperature Modules – Expansion Modules
It is a PLC Expansion module.
Used to increase the input capacities and functions in installed systems.
Operates only with the CPU, does not operate alone (standalone).
Has 4 channels of universal input.
Input types include Thermocouple (B, E, J, K, N, R, S, T), PT-100, PT-1000, NTC (10k @ 25 degrees Celsius), 0 to 60 mVDC.
Supply: Internal supply.
Power Consumption: 2W Max. @ 24VDC.
Mounting Type: DIN Rail.
Input Channel: 4 channels universal input operating independently
Resolution: 15-bit resolution, $0.1^\circ\text{C}$ reading accuracy
Input Types:
PT-100 or PT-1000 type RTD (Accuracy %0.2 of full scale)
B, E, J, K, N, R, S, and T type Thermocouple (Accuracy%0.2 of full scale)
25°C @10kOhm NTC (Accuracy 0.2°C)
0…60mVDC (0.01mV reading accuracy)
Protection: Short circuit and sudden voltage surge protection
Connection Types (Wiring): Supports 2- and 3-wire connection types. Line resistance maximum 20Ω
Input Repetition Rate (Update Rate): 10Hz
Temperature: 0 degrees Celsius to +60 degrees Celsius (Non-freezing).
Humidity: 5% rH to 95% rH (Non-condensing).
Environment: Must be used in environments free of flammable and corrosive gases.