EPS-120

General features

• Short Circuit Protection
• Overload Protection
• Over Voltage Protection
• Rail Mounting
• Insulation Class (2)
• LED Indicator for Energy
• Aesthetic Design
• Easy Commissioning
• 100% Full Load Test

Voltage Range : 90 ~ 264VAC 47~63Hz
AC Current : 1.3A/ 230VAC
Yield: %87.5
Starting Current : 35A/230VAC
Leakage Current: <1mA/240VAC

DC Voltage : 24VDC
Rated Current : 5A
Current Range : 0 - 5A
Rated Power : 120w
Ripple and Noise : 120mVp-p
Voltage Tolerance : ± 1.0%
Installation and Rise Time : 1200ms,60ms/230VAC 2500ms,60ms/115VAC for full load
Standby time : 16ms/230VAC for 10ms/115VAC full load

Overload : Up to 105%~130% of rated output power
Protection type: Constant current limitation automatically returns to normal after the fault condition is cleared.
returns to work.
Over Voltage : 115%~135%29V – 33V / After removing the overvoltage conditions, normal operation is restored by restarting.
High temperature : The supply voltage is cut off and then reactivated when suitable operating conditions occur.

Operating Temperature and Humidity Values: -20℃~+60℃; 20%~95%RH
Storage Temperature and Humidity Values : -40℃~+85℃; 10%~95%RH
Temperature Coefficient: ±0.03%/℃(0~50℃)
Vibration : 10~500Hz, 2G 10 min./1 cycle, vibrations from X, Y, Z axes for 60 minutes

Width: 40 mm

Height : 125,2 mm

Depth : 113,5 mm

Weight : 0,6 kg